Gelişmiş Arama

Basit öğe kaydını göster

dc.contributor.advisorKılıç, Fuat
dc.contributor.authorAydoğan, Berra
dc.date.accessioned2023-09-18T08:15:10Z
dc.date.available2023-09-18T08:15:10Z
dc.date.issued2023en_US
dc.date.submitted2023
dc.identifier.citationAydoğan, Berra. Kuru tip transformatörlerde yalıtım malzemeleri mesafelerinin sonlu elemanlar yöntemiyle ve deneysel olarak incelenmesi. Yayınlanmamış yüksek lisans tezi. Balıkesir Üniversitesi Fen Bilimleri Enstitüsü, 2023.en_US
dc.identifier.urihttps://hdl.handle.net/20.500.12462/13378
dc.descriptionBalıkesir Üniversitesi, Fen Bilimleri Enstitüsü, Elektrik-Elektronik Mühendisliği Ana Bilim Dalıen_US
dc.description.abstractTransformatörler, elektrik enerji sistemlerinde kullanılan en verimli elektrik makinalarıdır. Soğutma şekillerine ve kullanım alanlarına göre yağlı tip ve kuru tip transformatör çeşitleriyle kullanılmaktadır. Kuru tip transformatörler, günümüz koşulları için kullanışlı sayılabilecek, bakım gerektirmeyen, yanıcı olmayan, patlama riskinin olmaması gibi özellikleri sebebiyle çoğu alanda tercih sebebidir. Transformatörler çalışma koşullarında arızaya sebebiyet vermeden, sürekli ve güvenli olarak çalışmaya uygun olmalıdır. Tüm bu koşullar sağlanırken müşteri talebini karşılayabilecek uygun maliyetler sunulabilmelidir. Kuru tip transformatör maliyeti, tasarım metotlarıyla doğrudan etkilenmektedir ve firmaların kendine has metotları da maliyeti ciddi oranda etkilemektedir. Yüksek kalite ile birlikte düşük maliyeti sağlamaya yönelik bu metotlar, ağırlıklı olarak transformatör dielektrik mesafeleri üzerine yapılmaktadır. Bu çalışmada, transformatör maliyetini doğrudan etkileyen, transformatör tasarımındaki dielektrik mesafelerin optimum değerleri üzerine çalışmalar yürütülmüştür. Kuru tip transformatör faz-toprak arası mesafeyi temsilen deneyler yapılmış ve sonuçlar sonlu elemanlar yönteminin mantığıyla çalışan Ansys Maxwell programı ile değerlendirilmiştir. Deneylerle kuru tip transformatör faz-toprak arası mesafesinde ortam koşullarına göre delinme gerilimleri tespit edilmiş olup, çıkan sonuçlara göre grafikler oluşturulmuştur. Her bir ortam koşulu için grafiğin yorumundan yola çıkılarak dielektrik mesafeye göre delinme gerilimi tahmin edilebilmektedir. Bu durum transformatör tasarımında optimum dielektrik mesafe seçimine dolayısıyla optimum maliyete olanak sağlamaktadır.en_US
dc.description.abstractTransformers are the most efficient electrical machines used in electrical energy systems. It is used with oily type and dry type transformers according to cooling types and usage areas. Dry-type transformers are preferred in most areas due to their features such as maintenance free, non-flammable, and no explosion risk useful for today's conditions. Transformers must be suitable for continuous and safe operation without fault in operating conditions. While all these conditions are met, appropriate costs should be able to meet the customer demand. The cost of dry type transformer is directly affected by the design methods and the unique methods of the companies also affect the cost seriously. These methods, which aim to provide low cost with high quality, are mainly made on transformer dielectric clearances. In this study, studies were carried out on the optimum values of dielectric clearance in transformer design which directly affect the transformer cost. Experiments were carried out representing the dry type transformer phase-ground clearance and the results were evaluated with the Ansys Maxwell program which works with the logic of the finite element method. With the experiments, the breakdown voltages were determined according to the ambient conditions in the dry type transformer phase-earth clearance and graphs were created according to the results. Based on the interpretation of the graph for each ambient condition, the breakdown voltage can be estimated according to the dielectric clearance. This situation enables optimum dielectric clearance selection in transformer design and thus optimum cost.en_US
dc.language.isoturen_US
dc.publisherBalıkesir Üniversitesi Fen Bilimleri Enstitüsüen_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.subjectKuru Tip Transformatörlerde Dielektrik Açıklıklar(Boşluklar)en_US
dc.subjectDelinme Gerilimien_US
dc.subjectKısmi Deşarjen_US
dc.subjectOptimum Dielektrik Açıklıken_US
dc.subjectSonlu Elemanlar Yöntemien_US
dc.subjectAnsys Maxwellen_US
dc.subjectDielectric Clearances in Dry Type Transformersen_US
dc.subjectBreakdown Voltageen_US
dc.subjectPartial Dischargeen_US
dc.subjectOptimum Dielectric Clearanceen_US
dc.subjectFinite Element Methoden_US
dc.titleKuru tip transformatörlerde yalıtım malzemeleri mesafelerinin sonlu elemanlar yöntemiyle ve deneysel olarak incelenmesien_US
dc.title.alternativeInvestigation of insulation materials clearances in dry type transformers with finite element method and experimentalen_US
dc.typemasterThesisen_US
dc.contributor.departmentFen Bilimleri Enstitüsüen_US
dc.relation.publicationcategoryTezen_US


Bu öğenin dosyaları:

Thumbnail

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster