dc.contributor.authorSezen, Serkan
dc.contributor.authorAktaş, Ahmet
dc.contributor.authorUçar, Mehmet
dc.contributor.authorÖzdemir, Engin
dc.date.accessioned2019-05-16T19:32:16Z
dc.date.available2019-05-16T19:32:16Z
dc.date.issued2017
dc.identifier.issn1300-0632
dc.identifier.urihttps://hdl.handle.net/20.500.12462/3737
dc.descriptionSezen, Serkan (Balikesir Author)en_US
dc.description.abstractIn this paper, the control of a multifunction grid-connected photovoltaic (PV) system with a three-phase three- level (3L) neutral point clamped (NPC) inverter is proposed, which can perform shunt active ltering. Normally, the shunt active ltering is achieved by detecting the harmonic and reactive currents of the nonlinear load and then injecting the compensating current into the grid. Therefore, the proposed system can inject PV power to a grid with power factor correction and current harmonic ltering features simultaneously. In addition, a single-stage compact and efficient transformerless power conversion topology is used in this paper for the grid-connected solar PV system with maximum power point tracking capability. In order to control the multilevel inverter-based combined system, a synchronous reference frame control technique and hysteresis current control pulse width modulation method have been applied. The system con guration and control strategy are veri ed and validated by simulations based on MATLAB/Simulink and implemented in real-time using the dSPACE DS1103 controller board. The simulation with experimental results indicates that the injected currents are sinusoidal and current total harmonic distortion is about 3.9%, lower than the IEEE 519 harmonic limit.en_US
dc.description.abstractIn this paper, the control of a multifunction grid-connected photovoltaic (PV) system with a three-phase three- level (3L) neutral point clamped (NPC) inverter is proposed, which can perform shunt active ltering. Normally, the shunt active ltering is achieved by detecting the harmonic and reactive currents of the nonlinear load and then injecting the compensating current into the grid. Therefore, the proposed system can inject PV power to a grid with power factor correction and current harmonic ltering features simultaneously. In addition, a single-stage compact and efficient transformerless power conversion topology is used in this paper for the grid-connected solar PV system with maximum power point tracking capability. In order to control the multilevel inverter-based combined system, a synchronous reference frame control technique and hysteresis current control pulse width modulation method have been applied. The system con guration and control strategy are veri ed and validated by simulations based on MATLAB/Simulink and implemented in real-time using the dSPACE DS1103 controller board. The simulation with experimental results indicates that the injected currents are sinusoidal and current total harmonic distortion is about 3.9%, lower than the IEEE 519 harmonic limit.en_US
dc.language.isoengen_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.subjectMühendisliken_US
dc.subjectElektrik ve Elektroniken_US
dc.subjectWalking Trajectory Generationen_US
dc.subjectZero Moment Pointen_US
dc.subjectİnverted Pendulumen_US
dc.subjectBiped Roboten_US
dc.titleDesign and operation of a multifunction photovoltaic power system with shunt active ltering using a single-stage three-phase multilevel inverteren_US
dc.typearticleen_US
dc.relation.journalTurkish Journal of Electrical Engineering and Computer Sciencesen_US
dc.contributor.departmentBalıkesir Üniversitesien_US
dc.identifier.volume25en_US
dc.identifier.issue2en_US
dc.identifier.startpage1412en_US
dc.identifier.endpage1425en_US